5. C300 Configuration Form Reference
5.4. IOLINK Block
Plain Text
Average Free
Bandwidth (%)
Maximum Free
Bandwidth (%)
I/O Link Cable Error History
Channel A
Channel B

I/O Link Status tab

The I/O Link Status tab contains statistics for the Series 8 IOMs residing on the IOLINK,
which are used for maintenance and performance monitoring of the IOLINK interface.
The following table summarizes the parameter data you can monitor on the I/O Link
Status tab of the configuration form for the selected IOLINK block.
Plain Text
Primary IOPs
IOP Block Name
Receive Channel
Channel A Errors
150
Parameter Name
IOLFREEBWCYCLEAV
G
IOLFREEBWCYCLEMI
N
IOLCHNHISTA
IOLCHNHISTB
Parameter Name
PRIBLOCKNAME
PRIRCVCHN
PRICHNERRA
Series 8 C300 Controller User's Guide
Honeywell
User
Configurable
No
No
No
Indicates the error
history of IOLINK Cable
A for the last 10 "one
minute" periods.
No
Indicates the error
history of IOLINK Cable
B for the last 10 "one
minute" periods.
User
Configurable
No
Indicates the
corresponding Primary
IOP/IOM Tag.
No
Indicates the channel
that is actively listening
to the transmitted
messages.
No
Shows the number of
I/O link channel A errors
encountered by the
Primary IOP.