4. C300 Controller Configuration
4.2. Create C300 Controller and CEE function blocks
Step
2
Enter the desired name of up to 16
characters or accept the default. Press
<Tab>.
Note: Tag Name is limited to 16
characters and when creating redundant
controllers, the last four characters of the
secondary controller tagname will be
_SEC. Therefore, you should create a
tagname no longer than twelve
characters to allow for the suffix of the
secondary controller tag name.
3
Enter the Item Name. Press <Tab>.
4
Enter a valid Device Index number. Use
odd numbers for primary controllers.
Press <Tab>.
5
Select Module is redundant check box if
you want the controller to be one of a
redundant pair. Then, the Secondary
Tag Name will appear in the Redundancy
Configuration box.
6
By default, the Alarming Enabled check
box is selected. Press <Tab>.
To disable alarming for the parameters in
the Advanced Configuration section,
clear the Alarming Enabled check box.
7
If you have the C300 battery backup,
clear the check box to allow the battery-
related soft failures and events to be
reported.
If you do not have the C300 battery
backup, select the check box to suppress
battery-related soft failures and events.
48
Action
Series 8 C300 Controller User's Guide
Honeywell
Result
Moves cursor to the Item Name field.
Moves cursor to Device Index field.
Moves cursor to Module is redundant
check box.
C300 Controller is configured as either
non-redundant or redundant with a
Secondary C300 Controller block added
when the Primary controller FB
configuration form is closed.
Moves cursor to the Disable Battery
Alarm and Soft Fail field.
Moves cursor to the Temperature High
Alarm (degC) field.
R500
April 2017