Redundancy Link Status - Rdnlinkfailed; Controller Redundancy Specifications - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

Notification
Link
on the redundancy private path. The RDNSYNCSTATE
parameter is set to either PARTNERVISBL or INCOMPATIBLE.
This notification returns to normal if the controller is reconfigured
as redundant or if the partner is removed from the redundancy
link. For example, this notification is generated when the
redundancy cable of a loaded, non-redundant C300 is
connected to another C300. This notification is also be
generated when a partner Series 8 FIM module is added to a
redundant IOTA when the existing Series 8 FIM is explicitly
configured as nonredundant.

Redundancy Link Status - RDNLINKFAILED

The RDNLINKFAILED parameter is set ON when the redundancy cable is disconnected
and/or partner is not running. Once the redundancy cable is reconnected to a running
partner, the RDNLINKFAILED parameter is set OFF. Note that this parameter reflects
the physical status of the cable (connected vs. disconnected) and in no way indicates if
the redundancy cable is connected to a compatible partner. The 'Redundancy Link
Inactive' and 'Redundancy Link Active' notifications are generated when the
RDNLINKFAILED parameter is set ON and OFF, respectively.
8.9

Controller redundancy specifications

Control processing switchover interruption time
(
RDNSOTIMEMAX)
Initial synchronization time (from sync start to completion)
(
RDNISTIMEMAX)
Maximum elapsed time between commanded switchover and
completion of initial synchronization
Maximum elapsed time between switchover due to power
cycle of the primary and completion of initial synchronization
R500
April 2017
0. 8.9
Description
Specification
Series 8 C300 Controller User's Guide
Honeywell
8. C300 Redundancy operation
Controller redundancy specifications
RDNSYNCSTATE
500 milliseconds
200 seconds
300 seconds
300 seconds
223