7. C300 Controller Operation
7.4. Control Builder block icon descriptions
Icon
(red)
(red, simulation)
(red & white)
(white & red)
(yellow)
(yellow,
simulation)
(yellow & yellow)
(yellow &
shadow)
(blue)
(blue,
simulation)
(blue & white)
(blue & white,
pause)
(blue & yellow)
(blue & shadow)
(green)
188
Represents . . .
C300 is non-redundant and not communicating.
C300 is non-redundant. Simulation mode
enabled.
Primary C300 is not communicating.
Secondary C300 is not communicating.
C300 is non-redundant.
C300 is non-redundant. Simulation mode
enabled.
Primary C300 is not synchronized and partner
C300 is visible
Primary C300 is not synchronized and partner
C300 is absent or incompatible
C300 is non-redundant.
C300 is non-redundant. Simulation mode
enabled.
Primary C300 is synchronized.
Primary C300, standby synchronization.
Primary C300 is not synchronized and partner
C300 is visible.
Primary C300 is not synchronized and partner
C300 is absent or incompatible.
C300 is non-redundant.
Series 8 C300 Controller User's Guide
Honeywell
C300 Controller
(C300STATE)
No Communication
(Offnet)
No Communication
(Offnet)
No Communication
(Offnet)
No Communication
(Offnet)
No Database
No Database
No Database
No Database
Idle
Idle
Idle
Idle
Idle
Idle
Run or OK