Honeywell C300 User Manual page 261

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

Soft Fail Message
IOL Channel B Failure
IOL Maximum Errors
Exceeded
Not Active Supervisor
IOLIM Daughter Card
Soft Failure
Partner I/F Not Visible
On IOL
Partner I/F Mismatch
On IOL
IOL PROCESSOR
UNKNOWN SF
R500
April 2017
Condition when indicator is lit
Indicates that Channel B of the
IOLink has failed.
Shows the I/O link has exceeded the
maximum error limit.
Indicates that the IOL interface
daughter card could not transition into
the active supervisor role.
Indicates that a Daughter Card Soft
Failure exists.
Shows the Primary IOLINK is unable
to view it's redundant partner across
the I/O Link.
Indicates that the Secondary IOLINK
Partner is incompatible with the
Primary. The software versions may
be different.
Indicates a Daughter Card soft
failure.
Series 8 C300 Controller User's Guide
Honeywell
10. C300 Controller Troubleshooting
10.6. IOLINK block soft failures
Corrective Action
1. Check IOLINK cable B from end
to end for proper connections.
2. Check the cable connectors at
the IOTAs and fix as needed.
3. Refer to the IOLINK Statistics for
the error counts to zero in on the
culprit (Primary IOLINK, secondary
IOLINK, or IOMs) and replace if
necessary.
Once a problem has been
identified and a fix is applied, verify
the fix by:
(a) Reset the Error counts through
the I/O Link Command
"RESET_ERRORS" from the Main
Tab, then
(b) Re-enable the Periodic Cable
Swap diagnostic through the I/O
Link Command "ENB_PERSWAP"
from the Main Tab
(c) Monitor the error counts.
See "IOL Channel A Failure" and
"IOL Channel B Failure" Soft fail
Messages
Generally this is caused by a
partner IOLINK with conflicting
IOLINK Address (See Duplicate
IOL Address).
Call Honeywell TAC.
Applicable only to IOLIM.
Check/Replace the IOLINK
firmware application version.
Call Honeywell TAC.
Call Honeywell TAC.