7. C300 Controller Operation
7.2. C300 faceplate indicators/displays

Power and Status LEDs

LED Indication
Power LED
GREEN
Steady
Indicates the presence of 24Vdc to the controller module.
Status LED
GREEN
Steady
Non-redundant controller OK
Primary controller OK (primary and backup controllers may or may not be
synchronized)
GREEN
Primary OK with Soft Failure
Blink off once per
No database loaded (NODB)
second
(that is, 1 sec. ON,
1 sec. OFF)
ORANGE
Steady
Backup OK (controllers synchronized)
ORANGE
Backup OK with Soft Failure (or controllers are not synchronized)
Blink off once per
second
RED
steady
Selftest (POST) in progress, or Selftest has failed, Fault (hardware or
software diagnostic failed), or Hardware Watchdog Timer expired
RED
Operating in BOOT mode:
Blink off once per
Alive state - (ALIV on faceplate display) Operating in Boot firmware, IP
second
address assigned, primary address in use. No application image loaded, or
manually put in Alive state for loading.
Ready state - (RDY on faceplate display) Operating in Boot firmware, IP
address assigned, primary address in use. Valid application image loaded.
AND faceplate display is blank.
AND faceplate display is frozen.
AND display is - frozen or blank
RED
AND faceplate display shows:
Blink off once per
LOAD or PROG
180

Table 7 C300 Controller LED indications

Status/Description
Series 8 C300 Controller User's Guide
Honeywell
Hardware Watchdog Timer expired.
Indicates unrecoverable fault.
Unknown fault.
Indicates: Firmware download in