4. C300 Controller Configuration
4.6. Convert a redundant C300 Controller to a non-redundant controller
Step
4
Click OK.
5
Load the primary C300 block to the
controller.
6
Connect the Redundancy cable
between the redundant controller
pairs.
7
Perform the procedure
a Secondary C300 Controller
8
Select the Secondary C300
Controller icon. Perform a Load to
the controller.
9
Verify the redundant controller pair
achieves a synchronized state.
62
Action
To configure
block.
Series 8 C300 Controller User's Guide
Honeywell
Result
The C300 Controller configuration
form closes.
In the Project window:
The C300 Controller icon
indicates that it is configured as
redundant, (showing a double
controller icon). A double 'V'
sign is shown next to the
primary icon.
An additional C300 Controller
icon is created representing the
secondary controller.
The double 'V' disappears from the
primary C300 icon in the Project
view. The C300 block in the Monitor
view changes from a non-redundant
icon to a redundant icon.
A 'Not Synchronized' alarm may be
generated.
The double 'V' sign next to the
Secondary C300 icon disappears in
the Project view.
R500
April 2017