5. C300 Configuration Form Reference
5.1. C300 Controller Block
Plain Text
Uncorrectable
Internal RAM Sweep
Error
Corrected Internal
RAM Sweep Error
Uncorrectable User
RAM Sweep Error
Corrected User RAM
Sweep Error
IOLink (1) Soft Fail
Error
IOLink (2) Soft Fail
Error
Debug Flag Enabled
Minimum HW
Revision
Partner Not Visible
On FTE
Server History tab
The Server History tab is common to all configuration forms for tagged blocks in Control
Builder. The following table summarizes the parameter data you can monitor and
configure on this tab of the configuration form for the selected C300 block.
ATTENTION
The configuration settings you make for Server Load Options on the System
Preferences dialog box determines if the data entered on the Server History
tab is loaded to the Experion LX Server. Refer to the Control Building User's
112
Parameter Name
RAMSWEEPERR
RAMSCRUBERRS
BACKUPRAMSWEEPE
RR
BACKUPRAMSCRUBE
RRS
IOL1SOFTFAIL
IOL2SOFTFAIL
DEBUGFLAGSET
MINHWREVSF
PARTNERNOTVISFTE
Series 8 C300 Controller User's Guide
Honeywell
User
Configurable
No
Uncorrectable single-bit
errors in Main RAM.
No
Corrected single-bit errors
in Main RAM.
No
Uncorrectable single-bit
errors in Application RAM.
No
Corrected single-bit errors
in Application RAM.
No
Soft fail condition detected
on IOLink 1 interface.
Refer to the
block Main
No
Soft fail condition detected
on IOLink 2 interface.
Refer to the
block Main Tab.
No
Warning: Engineering
internal debug flag is set.
No
No
Indicates redundant
module partner is not
visible on FTE.
Notes
IOLink 1
Tab.
IOLink 2
R500
April 2017