7.3

C300 faceplate display indications

Controller display during normal operation

The C300 Controller faceplate display rotates through the following fields during normal
operation, executing the loaded Application firmware:
<Device Index> -> <Controller (CEE) State>-> <Redundancy Status>
For example, the display for a non-redundant or primary redundant controller shows:
#003 -> RUN -> sync
Table 10 lists the possible display indications for controllers operating normally in
application mode.

Table 10 Display indications when controller is in application mode

Display
Primary
Indications
Controller
for...
Device Index
#nnn
Controller
NOEE /
State
NODB / IDLE
/ RUN / OK
Redundancy
-np-
Status
!cpt
!syn
xxx%
sync
stby
nrdn
R500
April 2017
Secondary
Controller
#nnn
FTE Device Index, where nnn can be 001 to
255. Does not change with redundancy role.
BKUP
Implies redundancy role.
See Table 6 and Table 8 for a description of
each controller state indication.
-np-
No secondary/primary partner.
!cpt
Non-compatible partner visible
!syn
Partner controller visible, but not
synchronized and initial sync not in progress.
xxx%
Initial sync is in progress, where xxx can be
000 to 100 to indicate percentage complete.
sync
Redundant controller pair is synchronized.
stby
Backup controller in Standby Secondary
state (with retained database but normal
synchronization disabled).
(n/a)
Indication that primary controller is
configured as non-redundant.
Series 8 C300 Controller User's Guide