Honeywell C300 User Manual page 117

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

Plain Text
Battery State
Warning
Device Index
Switches Changed
Factory Data Error
ROM Application
Image Checksum
Failure
ROM Boot Image
Checksum Failure
WDT Hardware Error
WDT Refresh
Warning
Critical Task
Watchdog Warning
R500
April 2017
Parameter Name
BATTERYNOTOKSFTA
B
BCDSWSTS
FACTDATAERR
ROMAPPIMGCHKSMF
AIL
ROMBOOTIMGCHKSM
FAIL
WDTHWFAIL
WDTSWFAIL
TASKHLTHMON
Series 8 C300 Controller User's Guide
Honeywell
5. C300 Configuration Form Reference
5.1. C300 Controller Block
User
Configurable
No
Indicates the status of the
battery. Status is also
shown on Main tab of
C300 block.
The Battery State Warning
soft failure condition is
indicated when the C300
does not have a battery
backup and the "Disable
Battery Alarm and Soft
Fail" field in the Main tab is
not checked.
No
Online diagnostic warning:
Switches broken or
deliberately changed.
No
Online diagnostic error
reading factory data.
No
Online diagnostic error:
ROM application image
may be corrupted.
No
Online diagnostic error:
ROM boot image may be
corrupted.
No
Online diagnostic error:
Fault detected in the
Watchdog Timer hardware
circuit.
No
Online diagnostic warning:
Watchdog Timer is being
refreshed late and close to
the timeout limit.
No
A key task within the
controller is executing less
frequently than normal.
Notes