Non-Redundant C300 Controller With Memory Retention - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

10. C300 Controller Troubleshooting
10.10. Communication and system time faults during startup
Controller
Faceplate
icon
Status
Blinking
Green
LED
FTE
Blinking
Green
LEDs
Display
NODB
C300 appears to startup
CB
Grey
normally but Control Builder
icon
cannot communicate with the
C300 Controller. Hence, it
attempts to load or reload
C300 fail. If C300 was loaded
before a power cycle, its
associated icons in the
Monitor tab will be Red.
Status
Blinking
Green
LED
FTE
Blinking
Green
LEDs
Display
NODB
CB
Yellow
icon

Non-redundant C300 Controller with Memory Retention

Controller
Faceplate
Status
Blinking
Red ->
LED
Green
FTE
Off
LEDs
258
Problem
Communication on FTE
network
No communication
through CDA
Established connection
to system time source
None. Normal operation for
non-redundant controller
with no battery backup
following a power cycle.
Problem
No comm
unication on FTE
network.
Series 8 C300 Controller User's Guide
Honeywell
C300 Block
Station Alarm
Time Source
SNTP
CDA comm
Lost Connection
SNTP
C300 Not
Synchronized
C300 Block
Station
Time Source
Internal
C300 O FFNET
Resolve
Not e 4
None.
Alarm
Res
olve
Not e 1
R500
April 2017