3. C300 Controller Installation and Upgrades
3.2. C300 Controller installation
C300 IOTA Board
FTE A, FTE B
REDUNDANCY
MEMORY HOLD-UP
GPS (Currently not used)
FTE DEVICE INDEX
99, 10, 1
Prerequisites
Before you install the C300 Controller you should have:
A control cabinet installed with panel for mounting Series 8 control hardware.
A Series 8 power supply and optional battery backup hardware installed in the
cabinet.
Following are the parts included:
C300 Controller assembly (control module with IOTA board and mounting
hardware)
2 STP Cat5 Ethernet cables (one Yellow cable, one Green cable)
2 or 4 IOLink cable assemblies for connecting on-board IO Link interface if the
controller is supporting Series 8 I/O
Ensure the cabinet enclosure is connected to a protective earth ground using #8 AWG
solid copper wire. There should be metal to metal contact between the grounding bus
bar and the enclosure as well as the channel.
34
Fault Tolerant Ethernet (FTE) network
connectors
FTE A network cable connectors are Yellow.
FTE B network cable connectors are Green.
Redundant private path cable connector.
Redundancy cable connector is
Battery Backup cable connector
Battery cable is a twisted pair.
GPS cable connector
Three rotary decimal switches used to set the
FTE network address (Device Index) of the
controller.
Refer to the
procedure
Series 8 C300 Controller User's Guide
Honeywell
Description
Orange
C300 Controller Installation
for setting the address.
R500
April 2017