7.5
Activate C300 Controller's CEE
For the controller to begin executing its control strategy, you must activate the CEEC300
block.
Initial activation order guidelines
Make the initial activation of control strategy components in Control Builder from the
Monitoring tab in the following suggested order to minimize possible bad data generated
alarms.
Order
1
Control environment components such as:
CEEC300
2
Series 8 Input/Output Modules (IOMs)
3
Control Modules (CMs) and/or Sequential Control Modules (SCMs)
Activating the CEE
To activate the CEEC300 block, perform the following steps.
Step
1
From the Monitoring Tree, right-click CEE.
2
Click Change State.
3
Click Yes from the pop-up window to set the selected item active.
R500
April 2017
Component
Action
Series 8 C300 Controller User's Guide
Honeywell
7. C300 Controller Operation
7.5. Activate C300 Controller's CEE
191