7.5

Activate C300 Controller's CEE

For the controller to begin executing its control strategy, you must activate the CEEC300
block.

Initial activation order guidelines

Make the initial activation of control strategy components in Control Builder from the
Monitoring tab in the following suggested order to minimize possible bad data generated
alarms.
Order
1
Control environment components such as:
CEEC300
2
Series 8 Input/Output Modules (IOMs)
3
Control Modules (CMs) and/or Sequential Control Modules (SCMs)

Activating the CEE

To activate the CEEC300 block, perform the following steps.
Step
1
From the Monitoring Tree, right-click CEE.
2
Click Change State.
3
Click Yes from the pop-up window to set the selected item active.
R500
April 2017
Component
Action