Honeywell C300 User Manual page 150

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

5. C300 Configuration Form Reference
5.4. IOLINK Block
Plain Text
Channel B Errors
Channel B Silences
Channel B- Edges
Channel B+ Edges
Last Error
Processor Status
Last IOL Command
144
Parameter Name
PRIIFCHNERRB
PRIIFCHNSILB
PRIIFCHNMNB
PRIIFCHNPLB
PRIIFCOMMERR
PRIIFSTS
LASTIOLCMD
Series 8 C300 Controller User's Guide
Honeywell
User
Configurable
No
The number of I/O link
channel B errors
encountered locally by
the primary link
interface.
No
The number of I/O link
silences on channel B
encountered locally by
the primary link
interface.
No
The number of I/O link
channel B missed
minus edge transitions
encountered locally by
the primary link
interface.
No
The number of I/O link
channel B missed plus
edge transitions
encountered locally by
the primary link
interface.
No
The last I/O link
communications error
experienced by the
primary link interface.
The status of the link
No
processor for the
primary link interface.
No
The last I/O link
command requested
through the COMMAND
parameter or the last
SELECT_CH_A /
SELECT_CH_B
command automatically
issued when periodic
channel swap is
enabled.