Synchronization States - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

RDNCMPT
Parameter
PLATFORM
NodeNumber
HardwareType
FirmwareType
MessageFmt
PartnBootFmw
8.4

Synchronization states

The RDNSYNCSTATE parameter indicates the controller's synchronization state. Given
a redundant controller pair, synchronization is the act of transferring configuration and
execution data from the primary controller to the secondary so that the secondary has the
same information as the primary when it is needed to transition into the primary role.
Synchronization is only possible for a compatible redundant controller pair; when a
compatible partner is found, the controller transitions from the 'No Partner State' to the
'Partner Visible State.' Initial-sync is the act of performing first time transfer of
synchronization data; during this time the controllers are in the 'Sync in Progress' State.
The redundant controller pair enters the 'Synchronization Maintenance State' upon initial-
sync completion. While in the Synchronization Maintenance State, the secondary is a
viable replacement for the primary controller, and only that configuration data that is
changed and the control data that changes as a consequence of primary controller
execution is synchronized to the secondary controller.
R500
April 2017
State
Incompatible
Mismatched compatibility types (that is, different
platform firmware).
Incompatible
Device Indexes of potential redundant partner modules
are not properly configured as consecutive odd/even
pair.
Incompatible
Mismatched factory data (that is, different platform
hardware).
Incompatible
Mismatched compatibility types (that is, different
platform firmware).
Incompatible
The partner compatibility message format is undefined
or not supported.
Incompatible
The partner module is executing from boot firmware
(for example, partner is in the Alive, Ready, or Fail
State). To be compatible, both partners must be
executing from application firmware.
Series 8 C300 Controller User's Guide
Honeywell
8. C300 Redundancy operation
8.4. Synchronization states
Description