4 Packing, transportation & storage
This chapter contains all the information necessary for the correct packing, transportation and
unpacking of the UPS.
IF THE UPS IS NOT INSTALLED IMMEDIATELY, THE FOLLOWING
GUIDELINES MUST BE FOLLOWED:
TRANSPORT:
UPS CABINETS AND/OR BATTERY CABINETS CAN FALL OVER. USE THE
SHIPPING BRACKETS ON THE REAR AND FRONT TO SECURE THE
CABINETS. DO NOT TILT THEM MORE THAN 10° FROM VERTICAL,
OTHERWISE THE CABINETS MAY TIP OVER.
POTENTIAL DANGERS:
- TILTING THE CABINET MIGHT DAMAGE THE SYSTEM AND
THEREFORE IT SHOULD NOT BE CONNECTED TO THE MAINS.
- IF IT TIPS, THE WEIGHT OF THE UPS COULD CAUSE SERIOUS
INJURIES TO PERSONS OR DAMAGE TO EQUIPMENT IN THE
NOTE!
VICINITY.
STORAGE:
- THE UPS SHOULD BE STORED IN THE ORIGINAL PACKING AND
SHIPPING CARTON.
- THE RECOMMENDED STORING TEMPERATURE FOR THE UPS AND
BATTERIES IS BETWEEN +20°C AND +25°C.
- THE UPS AND THE BATTERY SETS MUST BE PROTECTED FROM
HUMIDITY > 95% (NON-CONDENSING).