16.3 Single input feed (standard version)
16.3.1 Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected.
16.3.2 Cable sections
Load
Frame type
in kW
Fuse A
(Agl/CB)
UPScale ST 40
40
3 x 80 A
UPScale ST 60
60
3 x 125 A
UPScale ST 80
80
3 x 160 A
UPScale ST120
120
3 x 224 A
UPScale ST 200
200
3 x 350 A
Modifications reserved
Page 23/26
Input 3 x 400 V/230 V
Cable A (mm
2
)
Max. input current
with battery charging [A]
(IEC 60950-1)
5 x 16
68 A
5 x 35
102 A
5 x 50
136 A
4 x 95+1 x 50
208 A
(PE)
5 x 185
333 A
Output 3 x 400 V/230
V @ cosphi 1.0
Fuse E
Cable D (mm
2
)
I nom
+ / N / -
[A]
(IEC 60950-1)
(Agl/CB)
5 x 16
58 A
5 x 35
87 A
5 x 50
116 A
3 x 224 A*1
5 x 70
174 A
3 x 300 A*1
5 x 185
290 A
3 x 450 A *1
*1 only valid for common battery use
Battery
Cable E (mm
)
2
for CBAT UPScale 120
or 200 ONLY
+ / N / -
Com.
Sep.
battery
Battery
NOT ALLOWED
3 x 95 *1
4x(3x10)
3 x 150 *1
6x(3x10)
3x(2x95)*1
5x(3x25)