Battery characteristics

Module type
Battery type
No. VRLA 12 V battery blocks
@ max. rated output power
Allowed no. of 1.2 V NiCd cells
@ max. rated output power
Floating voltage
End of discharge voltage
Maximum charging current
per module
Battery charging curve
Temperature compensation
Battery test
2)
Min battery block range allowed under following conditions:
Module type
No. VRLA 12 V battery blocks
Max power
Max autonomy
Modifications reserved
Page 8/26
UPScale M10
-
Maintenance-free VRLA or NiCd
-
30
- 50
2)
-
300
2)
- 500
VDC
VRLA: 2.25 V/cell - NiCd: 1.4 V/cell
VDC
VRLA: 1.65 V/cell - NiCd: 1.05 V/cell
4 (6 A charger is optional)
A
-
Ripple-free; IU (DIN 41773)
-
Standard (temp. sensor optional)
-
Automatic and periodically (adjustable)
UPScale M10
30-32
34-50
-
kW
6
10
10
min
any
5
any
UPScale M20
40
- 50
2)
400
2)
- 500
UPScale M20
40-46
48-50
16
20
20
any
5
any