3.3 Multi cabinet configuration
The DPA UPScale ST S2 may be paralleled to increase the power capacity up to 400 kW in steps of
10 or 20 kW. A maximum of 20 modules can be paralleled. The following system configurations are
available:
DPA UPScale S2
Number of modules
per frame
Parallel frames
per system
Max number of
modules per system
Max. total system
capacity w/o redundancy
The multiple cabinet systems are delivered with:
System graphical display
Parallel interface
Parallel cable
The start-up of a multiple cabinet systems is an operation which can be performed by a service
engineer form the manufacturer or by a service engineer from an agent certified by the manufacturer.
Please refer to the service manual to perform this operation.
Modifications reserved
Page 15/79
ST40
ST60
2
3
4
4
8
12
160 kW
240 kW
UPS A
UPS B
•
-
•
•
•
•
Fig 3.3-1: Multi cabinet configuration
ST80
ST120
4
6
4
3
16
18
320 kW
360 kW
UPS C
-
•
-
ST200
10
2
20
400 kW