7.4 Adding & replacement of a power module
7.4.1 In a single-module system
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED
BY A SERVICE ENGINEER FROM THE MANUFACTURER OR FROM AN
AGENT CERTIFIED BY THE MANUFACTURER
WARNING!
7.4.1.1 How to extract a ups-module in single module systems
THE WEIGHT OF A UPS MODULE CAN REACH 22KG, THEREFORE IT CAN
BE LIFTED BY 1 PERSON. WE RECOMMEND TWO PERSONS FOR
CARRYING THE MODULE.
POTENTIAL DANGERS:
THE UPS MODULE, DUE TO ITS WEIGHT, CAN CAUSE SERIOUS INJURY
OR DAMAGE SHOULD IT BE REMOVED INAPPROPRIATELY AND FALL.
WARNING!
SUITABLE LIFTING TOOLS AND SAFETY EQUIPMENT SUCH AS
SAFEGUARD PLATFORMS TO HANDLE THE EVENTUALITY OF A MODULE
BEING DROPPED SHOULD BE PLANNED
If your DPA UPScale
TM
extract the module:
1. Reset the alarm on the faulty module. The audible noise will stop. If the alarm condition
persists (the LED indicator ALARM will remain red) it means that there is a fault in the UPS
module.
2. If the load is supplied by the mains in bypass-mode (eco-mode) the maintenance bypass (IA1)
may be closed by turning it to position "ON".
NOTE: If the load is on inverter, then before closing the maintenance bypass IA1, transfer load
to bypass by means of the command "LOAD TO BYPASS" in submenu COMMANDS. On
LCD: "LOAD NOT PROTECTED" will appear.
3. Close maintenance bypass switch IA1 (position ON)
On LCD: "MANUAL BYP IS CLOSED" will appear and the LED-indicator will indicate as shown
below:
LED Indicator
LINE 1
LINE 2
BYPASS
INVERTER
BATTERY
THE LOAD IS NOW DIRECTLY SUPPLIED BY MAINS AND IS NOT PROTECTED
Modifications reserved
Page 57/79
NOTE:
WE RECOMMEND THAT THE MODULES ARE HANDLED BY TWO
PERSONS.
consists of only one single UPS-module then perform following steps to
Color
Green
Green
Green
RED
Green