3 Installation

3 .1 Delivery, transportation, positioning and storage

3 .1 .1 Receipt of the UPS and visual inspection

When receiving the UPS, carefully examine the
packing container and the UPS for any signs of
physical damage.
WARNING
The packing container of the UPS protects it
from mechanical and environmental damage.
To increase protection, the UPS is wrapped in a
plastic sheet. Keep the packaging for later re-use.

3 .1 .2 Unpacking list

After examining the package, open the box
and check the following items are included:
• 1 x PowerValue 11 RT G2 UPS
• 1 X USB with complete documentation in 5
languages
• Multi-language quick installation guide
• 2 x UPS stands (support)
• 8 x M4 hex screw with spring washer
(UPS stands)
• 8 x M4 pan washer screw (UPS stands)
• 8 x M4 flat screw (for rack mount ear)
• Rack-mount ear
• 1 x Schuko-IEC C13 cable (only for 1KB/1KS)
• 1 x Schuko-IEC C19 cable
(only for 2KB/2KS/3KB)
• Input power cord
(Australian models - AU/NZ type plug)
• 1 x IEC C13-C14 cable
• 1 x IEC C19-C20 cable (only for 3KB/3KS)
• 1 x external battery cable (only for S models)
• 1 x USB cable
• 1 x M16 cable gland (only for 3KS model)
• 1 x fixing plate for battery cable
IN CASE OF RECOGNIZABLE DAMAGE: DO
NOT CONNECT ANY VOLTAGE TO THE UNIT
/DO NOT PUT THE UNIT INTO OPERATION
Rack-mounting accessories (full rack-mounting
kit can be purchased separately):
• 2 x Rack-mount ear
• 8 x M4 screw (rack-mount ears)
Examine the UPS for any signs of damage and
ensure that the received UPS corresponds to the
material indicated in the delivery note. Notify
your carrier or supplier immediately in case of
any damage.

3 .1 .3 Operation of UPS

The UPS system contains no user-serviceable
parts. If the battery service life (3~5 years at 25°C
ambient temperature) has been exceeded, the
batteries must be replaced. In this case, please
contact your dealer.
Be sure to deliver the spent battery to a
recycling facility or ship it to your dealer in the
replacement battery packing material.

3 .1 .4 Storage of UPS

Before storing, charge the UPS 5 hours. Store the
UPS covered and upright in a cool, dry location.
During storage, recharge the battery in
accordance with the following table:
Storage temperature Recharge frequency Charging duration
-25°C - 40°C
Every 3 months
40°C - 45°C
Every 2 months
1-2 hours
1-2 hours