UPS INSTALLATION GUIDE
TLE Series
625 to 1000 kVA UL S2
TLE Series 1000
TLE Series 625 & 750

Advertisement

Table of Contents
loading

Summary of Contents for ABB TLE 625 Series

  • Page 1 — UPS INSTALLATION GUIDE TLE Series 625 to 1000 kVA UL S2 TLE Series 1000 TLE Series 625 & 750...
  • Page 2 The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of ABB. The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
  • Page 3 UPS. Thank you for choosing ABB! Start-up and commissioning! An ABB Global Services Field Engineer must perform start-up and commissioning of the UPS. Please contact ABB Service Center at least two weeks prior to schedule start-up and commissioning at 1-800-292-3739.
  • Page 4 While every care has been taken to ensure the completeness and accuracy of this manual, ABB assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
  • Page 5: Table Of Contents

    5/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Table of content Page Safety rules .................................. 6 Safety symbols and warnings ............................8 Cyber security .................................. 8 Layout ..................................9 Layout TLE Series 625 & 750 ............................9 Layout TLE Series 1000 ..............................
  • Page 6: Safety Rules

    This may require additional field marking or labelling defining appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries. Contact our ABB Service Center for product specific information. Installation This UPS must be installed and connected only by trained personnel.
  • Page 7 7/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Safety instructions when working with Battery Danger! External Battery must be installed and connected to the UPS by Qualified Service Personnel. Installation Personnel must read this entire section before handling the UPS and Battery. Full voltage and current are always present at the Battery terminals.
  • Page 8: Safety Symbols And Warnings

    8/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 1.1 Safety symbols and warnings Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads.
  • Page 9: Layout

    9/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Layout 2.1 Layout TLE Series 625 & 750 µP SNMP Fig. 2.1-1 TLE Series 625 & 750 - General view Fig. 2.1-3 Control Panel Fig. 2.1-5 Manual switches Q1 Fig.
  • Page 10 10/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B J35µP Fig. 2.1-6 TLE Series 625 & 750 - General view without protection panels Opening for top cable entry (* - for Utility input and Load output connection) Opening for top cable entry (* - for External Battery connection) Opening for bottom cable entry (* - for Utility input and Load output connection) Opening for bottom cable entry (* - for External Battery connection)
  • Page 11: Layout Tle Series 1000

    11/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 2.2 Layout TLE Series 1000 µP SNMP Fig. 2.2-1 TLE Series 1000 - General view Fig. 2.2-3 Control Panel Fig. 2.2-5 Manual switches Q1 Fig. 2.2-4 Connectivity Rack Fig.
  • Page 12 12/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B J35µP Fig. 2.2-6 TLE Series 1000 - General view without protection panels Opening for top cable entry (* - for Utility input and Load output connection) Opening for top cable entry (* - for External Battery connection) Opening for bottom cable entry (* - for Utility input and Load output connection) Opening for bottom cable entry (* - for External Battery connection)
  • Page 13: Environment

    UPS packing materials must be recycled in compliance with all applicable regulations. Recycling at the end of service life! ABB, in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
  • Page 14: Installation

    14/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Installation 4.1 Transport The UPS is packaged on a pallet suitable for handling with a forklift. The UPS must be moved in upright position. Do not tilt cabinets more than +/- 10° during handling. Move the UPS in its original package to the final destination site.
  • Page 15: Dimensions And Weights Tle Series 625 To 1000

    15/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.1.1 Dimensions and weights TLE Series 625 to 1000 Dimensions and weights TLE Series 625 & 750 54.73" 1390 mm 63.39" 118.12" 1610 mm 34.06" 3000 mm 865mm Dimensions (W x D x H): 118.12 x 34.06 x 75.00 inches / 3000 x 865 x 1905 mm...
  • Page 16: Delivery

    4.2 Delivery When delivered, inspect the package integrity and the physical conditions of the cabinets carefully. In case of any damage sustained during transport, immediately inform the carrier and contact your local ABB Service Center. A detailed report of the damage is necessary for any insurance claim.
  • Page 17: Place Of Installation

    4.4 Place of installation 4.4.1 UPS location Note! UPS installation and connection must be performed only by an ABB Service Technician! If optional cabinets and accessories are included with the UPS, please refer to those accompanying manuals for installation and operating instructions.
  • Page 18 18/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 625 to 1000 Opening for input and output cable connections 2.00 " / 51 mm Power Section cabinet In/Out Section cabinet TLES_UL_625-750_S2_UPS view top_ABB_01US 7.88 "...
  • Page 19 19/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Fixing of the UPS cabinet TLE Series 625 to 1000 on the floor Detail A The UPS cabinet is free standing normally does not require to be TLE Series 625 &...
  • Page 20 20/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 2.13 " / 54 mm Power Section cabinet In/Out Section cabinet TLES_UL_1000_S2_UPS fixing_ABB_02 2.37 " 3.94 "/100 mm 3.94 "/100 mm Frontal side 60 mm 27.56 " / 700 mm 27.56 "...
  • Page 21: Battery Location

    21/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.4.2 Battery location Battery require a well-ventilated room with controlled temperature to obtain reliable operation. The Battery can be installed immediately adjacent to the UPS (left or right side) or remotely from the UPS. If the Battery is installed remotely from the UPS, a wall mounted DC disconnect device must be installed within line-of-site to both the UPS and the Battery.
  • Page 22: Ventilation And Cooling

    In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air exhaust flow rate requirement of the UPS system. Contact your ABB Service Center for appropriate solutions. The below table indicates the heat dissipation at full Load at PF = 1 and charged Battery, up to 3280 ft (1000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
  • Page 23: Unpacking

    • The documentation includes the “Installation Guide & User Manual” and the “UPS Safety Rules”. Packing material recycling ABB, in compliance with environment protection, use only environmentally friendly material. UPS packing materials must be recycled in compliance with all applicable regulations.
  • Page 24 UPS as indicated in the appropriate label! PROTECTIVE The removal of the "Protective Foil" should be FOIL to remove as indicated performed only by an ABB Service Technician! in the label Packing material recycling! ABB, compliance with environment protection, uses only environmentally friendly material.
  • Page 25: Inter Cabinet Connections

    25/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.7 Inter cabinet connections 4.7.1 Cabinets positioning and interconnection for electrical safety grounding Note! The “Power Section cabinet” and “In/Out Section cabinet” must be installed on levelled floor. Mechanical interconnection is essential to ensure the electrical safety grounding of the “Power Section cabinet”.
  • Page 26 26/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 1000 - Cabinets positioning and interconnection Fixing type 3a 6 Bolt M6x12 Fixing type 2 8 Bolt M6x12 Power Section cabinet TLE Series 1000, in standard version, In/Out Section cabinet...
  • Page 27: Bus Bars Interconnection

    TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.7.2 Bus bars interconnection Note! All the bus bars interconnection must be performed only by an ABB Service Technician! TLE Series 625 & 750 - Bus bars interconnection Power Section cabinet In/Out Section cabinet...
  • Page 28 28/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 1000 - Bus bars interconnection Power Section cabinet In/Out Section cabinet Bus bars interconnection L1 Inverter L2 Inverter L3 Inverter L1 Rectifier L2 Rectifier L3 Rectifier N - Neutral Detail showing bus bars interconnection...
  • Page 29: Control Cables Interconnection

    TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.7.3 Control cables interconnection Note! All the cables interconnection must be performed only by an ABB Service Technician! TLE Series 625 & 750 - Control cables interconnection Power Section cabinet In/Out Section cabinet...
  • Page 30 30/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B XTR2A Power Section cabinet In/Out Section cabinet H9-10-11 H13-14-15 XTR2A connector H9-10-11 H13-14-15 XTR2A The cables must be fixed and do not touch the bus bars Fig.
  • Page 31 XD2 - HAN Connector male (32 poles) “Power Section” cabinet “In/Out Section” cabinet Note! All these connections must be performed only by an ABB Service Technician! Proper dressing needs to be done for each cable assembly in order to reduce the stress.
  • Page 32 32/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Power Section cabinet XTR2A In/Out Section cabinet H9-10-11 H13-14-15 XTR2A H9-10-11 H13-14-15 XTR2A connector The cables must be fixed and do not touch the bus bars Fig.
  • Page 33: Electrical Wiring

    Ensure that the AC and DC external isolators are OFF and locked out to prevent their inadvertent operation. Do not apply power to the equipment prior to the commissioning by an ABB Service Technician. Before any other input connection, connect and check the grounding wire.
  • Page 34: Input/Output Over Current Protection And Wire Sizing

    34/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.8.2 Input/output over current protection and wire sizing The cabling of the UPS system has to be sized according to the UPS power rating. Sizing of circuit Breakers, Fuses and cables for Input Utility, output load and Battery must meet the requirements of local and national electrical codes.
  • Page 35: Data For Input/Output And Battery Over Current Protection And Wire Sizing

    35/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.8.3 Data for Input/output and Battery over current protection and wire sizing Note! • Please read the safety precautions at the front of this guide carefully, and thoroughly review the Battery manufacturers installation and maintenance manual before connecting the Battery to the UPS.
  • Page 36 36/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Fig. 4.8.3-3 Dual Input Utility Rectifier & Bypass Fig. 4.8.3-4 Common Input Utility Rectifier & Bypass Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire, only connect UPS to a circuit provided with (See below) maximum amperes branch circuit over current protection in accordance with the NEC (National Electric Code), NSI / NFPA 70 F1 - AC Input Rectifier...
  • Page 37 37/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B NEC Section 210-20 (a) Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 140°F Trough 194°F (60°C Trough 90°C) Not More than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 86°F (30°C).
  • Page 38: Installation Requirements

    38/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.8.4 Installation requirements Typical examples for the connection of the TLE Series 625 to 1000. Single UPS with Common Input Utility for Rectifier & Bypass. Single UPS with Common Input Utility for Rectifier & Bypass, 3-wire distribution (3-phase plus ground) Single UPS with Dual Input Utility for Rectifier &...
  • Page 39 39/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B UPS Parallel System with Common Input Utility Rectifier & Bypass UPS Parallel System with Common Input Utility Rectifier & Bypass, 3-wire distribution (3-phase plus ground)
  • Page 40 40/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B UPS Parallel System with Dual Input Utility for Rectifier & Bypass (Connect a single input Neutral to Bypass Utility (inside the UPS, common Neutral for Bypass and Rectifier) UPS Parallel System with Dual Input Utility for Rectifier &...
  • Page 41: Wiring Connection

    4.9 Wiring connection Note! UPS installation and connection must be performed only by an ABB Service Technician! Refer to the “Safety prescriptions - Installation” described on Chapter 1. In case of UPS equipped with options or customized parts not covered by this manual, please consult the appropriate technical documentation before proceeding with electrical connections.
  • Page 42 42/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 1000 Access to the bus bars for the cable connections Top entry cables Battery Top entry cables Utility input & Load output Bottom entry cables Bottom entry cables Battery Utility input &...
  • Page 43 43/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 625 to 1000 Power connection bus bars configuration for the top cable entry or bottom cable entry The configuration of the TLE Series 625 to 1000 is with top cable entry as standard (see Fig. 4.9-3). It is possible to configure the bus bars with bottom cable entry (see Fig.
  • Page 44 44/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 625 to 1000 PE-Ground connection bus bar configuration for the top cable entry or bottom cable entry The configuration of the TLE Series 625 to 1000 is with top cable entry as standard. It is possible to configure the bus bar with bottom cable entry (see Fig.
  • Page 45: Tle Series 625 & 750 - Power Connection With Common Input Utility

    45/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.9.1 TLE Series 625 & 750 - Power connection with Common Input Utility Rectifier Interconnections links BR1, BR2 and BR3 Utility Typical installation must remain connected using common NEMA two hole lugs Load...
  • Page 46 46/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Note! This UPS is only designed to operate in a wye-configured electrical system with a solidly grounded neutral. The UPS cannot be operated from a mid-point or end-point grounded delta supply source. If the UPS is equipped with an input bypass transformer, the secondary of the transformer must be wye-configured with neutral solidly grounded If the Load requires a Neutral, a Bypass Source Neutral MUST BE PROVIDED.
  • Page 47: Tle Series 625 & 750 - Power Connection With Dual Input Utility

    47/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.9.2 TLE Series 625 & 750 - Power connection with Dual Input Utility Note! Connect a single input Neutral to Bypass Utility (inside the UPS, common Neutral for Bypass and Rectifier).
  • Page 48 48/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Note! This UPS is only designed to operate in a wye-configured electrical system with a solidly grounded neutral. The UPS cannot be operated from a mid-point or end-point grounded delta supply source. If the UPS is equipped with an input bypass transformer, the secondary of the transformer must be wye-configured with neutral solidly grounded If the Load requires a Neutral, a Bypass Source Neutral MUST BE PROVIDED.
  • Page 49 49/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 625 & 750 - Installation notices in case of power connection with Dual Input Utility Rectifier Interconnections links Utility Bypass BR1, BR2 and BR3 Utility must be removed! Load...
  • Page 50: Tle Series 1000 - Power Connection With Common Input Utility

    50/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.9.3 TLE Series 1000 - Power connection with Common Input Utility Interconnections links Rectifier BR1, BR2 and BR3 Utility must remain connected Typical installation using common NEMA two hole lugs Load L3-1...
  • Page 51 51/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Note! This UPS is only designed to operate in a wye-configured electrical system with a solidly grounded neutral. The UPS cannot be operated from a mid-point or end-point grounded delta supply source. If the UPS is equipped with an input bypass transformer, the secondary of the transformer must be wye-configured with neutral solidly grounded If the Load requires a Neutral, a Bypass Source Neutral MUST BE PROVIDED.
  • Page 52: Tle Series 1000 - Power Connection With Dual Input Utility

    52/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.9.4 TLE Series 1000 - Power connection with Dual Input Utility Note! Connect a single input Neutral to Bypass Utility (inside the UPS, common Neutral for Bypass and Rectifier).
  • Page 53 53/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Note! This UPS is only designed to operate in a wye-configured electrical system with a solidly grounded neutral. The UPS cannot be operated from a mid-point or end-point grounded delta supply source. If the UPS is equipped with an input bypass transformer, the secondary of the transformer must be wye-configured with neutral solidly grounded If the Load requires a Neutral, a Bypass Source Neutral MUST BE PROVIDED.
  • Page 54 54/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B TLE Series 1000 - Installation notices in case of power connection with Dual Input Utility Rectifier Interconnections links Utility Bypass BR1, BR2 and BR3 Utility must be removed! Load L3-1 L3-2...
  • Page 55: Use Of Tle Series 625 To 1000 In Eboost™ Operation Mode

    For systems intended to be operated in eBoost™ Operation Mode, the installation shall be protected with suitable surge protection devices (SPDs) on the AC bus feeding the UPSs. Please contact your ABB Service Centre for more information. Note! In eBoost Operation Mode the Inverter output filter is placed in parallel with the Load and combined with the Load current it contributes to the UPS input characteristic.
  • Page 56: Use Of Tle Series 625 To 1000 As Frequency Converter

    Avoid high inrush current due to transformer magnetization or motor starting. Note! Only an ABB Service Technician may change a unit from Frequency Converter into a normal UPS (with Bypass) or a normal UPS to a Frequency Converter (with Bypass).
  • Page 57: Rpa Parallel System Connection

    UPS Installation Guide / REV-B 4.10 RPA Parallel System connection Warning! This operation must be performed only by an ABB Service Technician before the initial start-up (ensure that the UPS installation is completely powered down). 4.10.1 Power wiring of parallel units...
  • Page 58: Parallel Control Bus Connection

    58/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 4.10.2 Parallel control bus connection In case of Parallel System, the communication between the units takes place through the Control Bus Cables. Each Parallel Unit contains the two boards “P13/P14 – IM0222 – Bus Interface Board” (mounted on top of the board “P12 –...
  • Page 59 59/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B J1B/1 Note! Final units, first and last, of an RPA Parallel System. On the two boards P13/P14 – IM0222 – Bus Interface Board, J1A/1 of the first and last units of a Parallel System, switches must...
  • Page 60: Control Bus Cable Location

    UPS Installation Guide / REV-B 4.10.3 Control bus cable location Warning! This installation must be performed and verified by an ABB Service Technician before the initial start-up. Ensure that the ups installation is completely powered down. Keep SELV cables separated from high voltage cables.
  • Page 61 It is important that the cable J1A – J2A (1/2/3/4/5) must be the same length as cable J1B – J2B (1/2/3/4/5). Warning! Connection and commissioning of an additional UPS to an existing Parallel System must be performed only by an ABB Service Technician.
  • Page 62: Epo - Emergency Power Off" Command Connection

    Warning! The connection of an emergency button EPO (Emergency Power Off) must be performed only by an ABB Service Technician when the UPS is completely powered down! Note! The reliability of the system depends on this contact NC (Normally Closed)! An Emergency button (Normally Closed voltage-free contact) can be connected on terminals XA / EPO-1, EPO-2.
  • Page 63 63/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Note! To operationalize this function, in case that the UPS was provided with one or more cards “P4 - Customer Interface” (max. 3 - see Chapter 5), there must be on each card the following: - Remove the cable short-circuiting terminals X2 / 1, 2 (see Fig.
  • Page 64: Tle Series 1000 - Wiring Of "Ip Ring Bus" (Option)

    They shall not be accessible to end user and not likely to be stress by pulling. Warning! All maintenance and service works must be performed by an ABB Service Technician only! The cover “A” must be always be mounted. If not serious injury or electrical shock could occur! TLE Series 1000 with “IP Ring Bus”...
  • Page 65: Connectivity Interface

    Fig. 9-2 Connectivity Slots Note! The installation of any option board must be performed only by an ABB Service Technician. Prior to the installation, connection and cabling of any option board the UPS must be completely powered down and all the power sources that will be connected to the option board must be de- energized.
  • Page 66: Serial Port J35Μp - Rs232 (Sub D, Female 9 Pin)

    J35µP - RS232 IMV protocol TLE Series 625 & 750 Total remote management of J35µP - RS232 the system using software iUPSGuard, Data Protection or ABB Service Software for system protection management systems. J35µP - RS232 TLE Series 1000 Fig. 5.1-1 TLE Series 625 to 1000 - Serial Port J35µP – RS232...
  • Page 67: Customer Interface Board

    67/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B 5.2 Customer interface board J1 connector– RJ45 8P8C (see Section 5.2.1) Pin 5: TX (out) Pin 6: RX (in) Pin 4: GND X1 terminal block – Output signals on voltage free contacts (see Section 9.2.2) X1 / 1, 2, 3 NO, C, NC MAINS FAILURE...
  • Page 68: Connector J1 - Rj45 8P8C

    In case different alarms or operating status are required, they can be configured on the same terminals via software from the Control Panel. The configuration can be changed in parameters mode by an ABB Service Technician using the appropriate “Service Code”.
  • Page 69: X2 Terminal Block - "Epo - Emergency Power Off

    “GENERATOR ON” on X1 / 11, 22. See Fig. 5.2-1 / X1. Since the Parameter for of the reading of the Generator function is “Service Code” protected, call the nearest ABB Service Centre for it's activation.
  • Page 70: X1 Terminal Block - Aux External Maintenance Bypass

    When this contact closes, eBoost or IEMi operation mode is inhibited. The Parameter for the activation of such function is “Service Code” protected. Contact your ABB Service Center for its activation. This function is particularly useful for controlling eBoost or IEMi operation following critical conditions on either the load side or the input Utility, including generator operation when the “GENERATOR ON”...
  • Page 71: Notes

    71/72 TLE Series 625 to 1000 PurePulse™ UL S2 UPS Installation Guide / REV-B Notes 6.1 Notes Form It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. Date Description Done by...
  • Page 72 — ABB Power Protection SA Via Luserte Sud 9 6572 Quartino Switzerland abb.com/ups © Copyright 2020 ABB. All rights reserved Specifications subject to change without notice...