5.7.3 Single input feed (standard version)
5.7.3.1 Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected.
5.7.3.2 Cable sections
Load
Frame type
in kW
Fuse A
(Agl/CB)
UPScale ST 40
40
3x80A
UPScale ST 60
60
3x125A
UPScale ST 80
80
3x160A
UPScale ST120
120
3x224A
UPScale ST 200
200
3 x 350 A
Modifications reserved
Page 40/79
Fig 5.7.3.1-1: Single input feed block diagram
Input 3x400V/230V
Cable A (mm
2
)
Max. Input Current
with battery charging [A]
(IEC 60950-1)
5x16
68 A
5x35
102 A
5x50
136 A
4x95+1x50 (PE)
208 A
5 x 185
333 A
Output 3x400V/230V @
cosphi 1.0
Fuse E
Cable D (mm
2
)
I nom
+ / N / -
[A]
(IEC 60950-1)
(Agl/CB)
5x16
58 A
5x35
87 A
5x50
116 A
3x224A*1
5x70
174 A
3x300A*1
5 x 185
290 A
3 x 450 *1
*1 only valid for common battery use
Battery
Cable E (mm
)
2
for CBAT UPScale 120
or 200 ONLY
+ / N / -
Sep.
Com. Battery
Battery
NOT ALLOWED
3x95 *1
4x (3x10)
3x150 *1
6x (3x10)
5 x
3 x (2 x 95)*1
(3x25)