Single Input Feed (Standard Version); Block Diagram; Cable Sections - ABB DPA UPScale ST40 User Manual

S2 family 10 – 200 kw
Table of Contents

Advertisement

5.7.3 Single input feed (standard version)

5.7.3.1 Block diagram

Cable sections and fuse ratings recommended. Alternatively, local standards to be respected.

5.7.3.2 Cable sections

Load
Frame type
in kW
Fuse A
(Agl/CB)
UPScale ST 40
40
3x80A
UPScale ST 60
60
3x125A
UPScale ST 80
80
3x160A
UPScale ST120
120
3x224A
UPScale ST 200
200
3 x 350 A
Modifications reserved
Page 40/79
Fig 5.7.3.1-1: Single input feed block diagram
Input 3x400V/230V
Cable A (mm
2
)
Max. Input Current
with battery charging [A]
(IEC 60950-1)
5x16
68 A
5x35
102 A
5x50
136 A
4x95+1x50 (PE)
208 A
5 x 185
333 A
Output 3x400V/230V @
cosphi 1.0
Fuse E
Cable D (mm
2
)
I nom
+ / N / -
[A]
(IEC 60950-1)
(Agl/CB)
5x16
58 A
5x35
87 A
5x50
116 A
3x224A*1
5x70
174 A
3x300A*1
5 x 185
290 A
3 x 450 *1
*1 only valid for common battery use
Battery
Cable E (mm
)
2
for CBAT UPScale 120
or 200 ONLY
+ / N / -
Sep.
Com. Battery
Battery
NOT ALLOWED
3x95 *1
4x (3x10)
3x150 *1
6x (3x10)
5 x
3 x (2 x 95)*1
(3x25)

Advertisement

Table of Contents
loading