Customer Interfaces: Input And Output Dry Ports - ABB DPA UPScale ST40 User Manual

S2 family 10 – 200 kw
Table of Contents

Advertisement

9.4

Customer interfaces: input and output dry ports

Block Terminal Contact
X 2 / 1
NO
X 2 / 2
NC
C
X 2 / 3
X 2 / 4
NO
NC
X 2 / 5
X 2 / 6
C
X 2 / 7
NO
NC
X 2
X 2 / 8
X 2 / 9
C
NO
X 2 / 10
X 2 / 11
NC
X 2 / 12
C
NO
X 2 / 13
X 2 / 14
NC
X 2 / 15
C
X1 / 1
X1 / 2
GND
X1 / 3
X1 / 4
GND
X1 / 5
X1
X1 / 6
GND
X1 / 7
X1 / 8
GND
X1 / 9
X1 / 10
GND
All voltage-free contacts are rated 60 VAC max. and 500 mA max.
All the interfaces are connected to Phoenix spring terminals with wires (0.5 mm
Modifications reserved
Page 13/26
Signal
On Display
MAINS_OK
ALARM
LOAD_ON_INV
Message
BATT_LOW
ALARM
LOAD_ON_MAINS
Message
COMMON_ALARM
ALARM
+ 12
IN
VDC
GND
+ 12
IN
VDC
GND
+ 3.3
IN
VDC
GND
+ 12
IN
VDC
GND
+ 12
IN
VDC
GND
Function
Mains present
Mains failure
Common
Load on inverter
(Load on mains bypass)
Common
Battery low
Battery OK
Common
Load on bypass (Mains)
(Load on inverter)
Common
Common ALARM (System)
NO alarm condition
Common
Generator operation
(NC = Generator ON)
Customer IN 1
(Function on request, to be defined)
Temperature battery
(If connected, the battery charger
current if depending on the battery
temp.)
Remote shutdown
(Do not remove the factory mounted
bridge until external remote
shutdown is connected)
12 VDC source
(max. 200 mA load)
2
)