16.4 Dual input feed (optional version)
16.4.1 Block diagram
Cable sections and fuse ratings recommended. Alternatively, local standards to be respected
16.4.2 Cable sections
Input 3 x 400 V/230 V
Frame
Load
type
in
UPScale
Fuse B
Cable B (mm
kW
ST
(Agl/CB)
(IEC 60950-1)
40
40
3 x 80 A
60
60
3 x 125 A
80
3 x 160 A
80
4 x 95+1 x 50
120
120
3 x 224 A
200
200
3 x 350 A
Modifications reserved
Page 24/26
Bypass 3 x 400 V/230 V
Max.
input
current
)
Fuse C
2
with
(Agl/CB)
battery
charging
[A]
5 x 16
68 A
3 x 80A
5 x 35
102 A
3 x 125A
5 x 50
136 A
3 x 160A
208 A
3 x 224A
(PE)
5 x 185
333 A
3 x 350 A
Output 3 x 400 V/230 V
@ cosphi 1.0
Cable C
Cable D
(mm
)
(mm
)
2
2
I nom
(IEC
(IEC
[A]
60950-1)
60950-1)
4 x 16
5 x 16
58 A
4 x 35
5 x 35
87 A
4 x 50
5 x 50
116 A
4 x 95
5 x 70
174 A
4 x 185
5 x 185
290 A
*1 only valid for common battery use
Battery
Cable E (mm
)
2
for CBAT UPScale 120 or
Fuse E
200 ONLY
+/N/-
+ / N / -
(Agl/CB)
Com.
Sep.
battery
battery
NOT ALLOWED
3 x 224
3 x 95 *1
4 x (3 x 10)
A*1
3 x 300
3 x 150 *1
6 x (3 x 10)
A*1
3 x 450
3x(2x95)*1
5 x (3 x 25)
A*1