15 Installation planning – UPS positioning
The minimum clearances as described below that are needed to allow proper airflow to the UPS
system, and to allow proper service and maintenance, should be respected.
DPA UPScale S2 cabinets
Back clearance for ventilation
A
(forced air outlet)
Front clearance needed to
B
allow correct door opening
Maximum door opening
C
angle
Top clearance
D
(Top clearance is only needed if
there is no side clearance)
Modifications reserved
Page 20/26
ST40, ST60, ST80, ST120
200 mm
UPS + battery
ST200
cabinets in row.
300 mm
1000 mm
115°
400 mm