5.3 UPS and battery location

The minimum clearances needed to allow proper airflow around the UPS, and to allow proper service
and maintenance, must be observed. They are detailed below:
DPA UPScale S2 Cabinets
Back clearance for ventilation
A
(forced air outlet)
Front clearance needed to
B
allow a correct door opening
Maximum door opening
C
angle
Top Clearance
D
(Top clearance is only needed if
there is no side clearance)
Modifications reserved
Page 27/79
Fig 5.3-1: UPS and battery location (Clearances)
ST40, ST60, ST80, ST120
200 mm
UPS + battery
ST200
cabinets in row.
300 mm
1000 mm
115°
400 mm