10 Multi-cabinet configuration

The DPA UPScale ST S2 may be paralleled to increase the power capacity up to 400 kW in steps of
10 or 20 kW. A maximum of 20 modules can be paralleled, into four frames.
The following system configurations are available:
DPA UPScale S2
Number of modules
per frame
Parallel frames
per system
Max number of
modules per system
Max. total system
capacity w/o redundancy
For a multiple-cabinet system, the following options are necessary:
Modifications reserved
Page 14/26
ST40
ST60
2
3
4
4
8
12
160 kW
240 kW
System graphical
display
Parallel interface
Parallel cable
ST80
ST120
4
6
4
3
16
18
320 kW
360 kW
UPS A
UPS B
X
-
X
X
X
X
ST200
10
2
20
400 kW
UPS C
-