5.6 External batteries

KEEP AWAY FROM BATTERY POLES AS THESE CARRY DANGEROUS DC
VOLTAGES THAT CAN CAUSE FATAL ACCIDENTS.
NOTE:
MANIPULATION OF THE BATTERY SYSTEM SHOULD ONLY BE
PERFORMED BY TRAINED SERVICE AND MAINTENANCE PERSONNEL
FROM THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS.
INAPPROPRIATE MANIPULATIONS OF THE BATTERIES CAN CAUSE
SPARKS. WHILE WORKING ON BATTERY SYSTEMS IT IS MANDATORY TO
WARNING!
WEAR PROTECTIVE GLASSES

5.6.1 External battery configuration

In the DPA UPScale
ST 80, ST 120 and ST 200 UPS cabinets there is no space provided for
TM
batteries.
There are two external matching battery cabinets available:
CBAT UPScale -120 for Separate or Common battery configurations of 24Ah or 28Ah blocks
(max. 120 Blocks)
CBAT UPScale-200 for Separate or Common battery configurations for 24Ah or 28Ah blocks
(max. 200 Blocks)
S-type = For Separate. Battery
C-type = For Common. Battery
Battery frames
Configuration accommodates:
Battery fuses / Max. Batt. Strings :
Terminals :
Battery fuses / Max. Batt. Strings
Terminals :
Fuse Type (Very Fast acting)
Dimensions (WxHxD)
Weight with trays and w/o batteries
For detailed information on, and layout of, the battery cabinets please refer to the "external battery
cabinets" chapter in the technical data sheet.
Modifications reserved
Page 34/79
CBAT-UPScale-120
S-type or C-type
120 Batt. block x
24Ah/28Ah
Max.
on 8 shelf
3x5=15 blocks/shelf
9 / 3
S-type
(Terminal 9 x 16/25mm2)
9 / 3
+ Com. Connection
C-type
Bar
3 x (2xM8) +PE 2xM8
3x100 A
A
730x1975x800
mm
290
kg
CBAT-UPScale-200
S-type or C-type
200 Batt. blocks x
24Ah/28Ah
on 7 shelf
6x5=30 blocks/shelf
15 / 5
(Terminal 15 x 16/25mm2)
15 / 5
+ Com. Connection
Bar
3 x (2xM10) +PE
2xM10
5x100A
1200x1975x800
410