14 Heat dissipation per module with nonlinear load

Module type
Heat dissipation with 100%
nonlinear load per module
(EN 62040-1-1)
Heat dissipation with 100%
nonlinear load per module
(EN 62040-1-1)
Airflow (25° - 30°C) with
100% nonlinear load per
module
(EN 62040-1-1)
Dissipation at no load
Modifications reserved
Page 19/26
UPScale M10
W
550
BTU/h
1887
m
3
/h
150
W
120
UPScale M20
1100
3754
150
150