TECHNICAL DATA, VACON® 100 FLOW
Table 47: The technical data of the VACON
Technical item or function
Ambient conditions
Ambient conditions
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
100 FLOW AC drive
®
Ambient operating tem-
perature
Storage temperature
Relative humidity
Air quality
Altitude
Pollution degree
Vibration:
EN61800-5-1
EN60068-2-6
Shock:
EN60068-2-27
Enclosure class
Technical data
I
current: -10°C (no frost)...+40 °C
L
Maximum operating temperature: +50 °C with derating
(1.5%/1°C)
-40 °C...+70 °C
0-95% R
, non-condensing, non-corrosive
H
Tested according to IEC 60068-2-60 Test Ke: Flowing
mixed gas corrosion test, Method 1 (H
sulfide] and SO
[sulfur dioxide])
2
Designed according to
Chemical vapours: IEC 60721-3-3, unit in opera-
tion, class 3C2
Mechanical particles: IEC 60721-3-3, unit in oper-
ation, class 3S2
100% load capacity (no derating) up to 1000 m
1-% derating for each 100m above 1000 m
Maximum altitudes:
208-240 V: 4000 m (TN and IT systems)
380-500 V: 4000 m (TN and IT systems)
380-500 V: 2000 m (corner-grounded network)
525-690 V: 2000 m (TN and IT systems, no corner
grounding)
Voltage for relay outputs:
Up to 3000 m : Allowed up to 240 V
3000-4000 m: Allowed up to 120 V
Corner-grounding:
up to 2000 m only (Requires a change in the EMC
level from C3 to C4, see 8.4 Installation in a cor-
ner-grounded network.)
PD2
5-150 Hz
Displacement amplitude 0.25 mm (peak) at 5-31 Hz
Maximum acceleration amplitude 1 G at 31-150 Hz
UPS Drop Test (for applicable UPS weights)
Storage and shipping: maximum 15 G, 11 ms (in pack-
age)
IP00 / UL Open Type
VACON · 121
S [hydrogen