POWER CABLING
Table 12: The recommended mains cables and fuses in 525-690 V
Enclosure
Type
size
0080 6
0080 7
0100 6
MR8
0100 7
0125 6
0125 7
0144 6
0144 7
0170 6
MR9
0170 7
0208 6
0208 7
0261 6
0261 7
0325 6
0325 7
MR10
0385 6
0385 7
0416 6
0416 7
0460 6
0460 7
0520 6
0520 7
0590 6
0590 7
MR12
0650 6
0650 7
0750 6
0750 7
0820 6
0820 7
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
IL [A]
Mains fuses per
phase (gG/gL) [A]
80
100
100
125
125
160
144
160
170
200
208
250
261
315
325
355
385
400
416
450
460
2 x 315
520
2 x 315
590
2 x 315
650
2 x 355
750
2 x 400
820
2 x 425
Mains and motor
Mains cable
cable (Cu/AI) [mm2]
terminal,
bolt size
[mm
3x35+16 (Cu)
3x50+21 (Al)
3x50+25 (Cu)
3x70+21 (Al)
3x70+35 (Cu)
3x95+29 (Al)
3x70+35 (Cu)
M10
3x120+41 (Al)
3x95+50 (Cu)
M10
3x150+41 (Al)
3x120+70 (Cu)
M10
3x185+57 (Al)
3x185+95
M12
2x(3x95+29)
3x240+120
M12
2x(3x120+41)
2x(3x120+70)
M12
2x(3x185+57)
2x(3x120+70)
M12
2x(3x185+57)
2x(3x150+70)
M12
2x(3x240+72)
2x(3x185+95)
M12
4x(3x95+29)
4x(3x70+35)
M12
4x(3x120+41)
4x(3x95+50)
M12
4x(3x150+41)
4x(3x120+70)
M12
4x(3x150+41)
4x(3x120+70)
M12
4x(3x185+57)
VACON · 47
Grounding
terminal,
bolt size
2
]
[mm
2
]
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
M8
6