Table 43: The technical data of the VACON
Technical item or function
Protections
* = For the motor thermal memory and the memory retention function to obey the UL
61800-5-1 requirements, you must use the system software version FW0072V007 or a newer
version. If you use an older system software version, you must install a motor
overtemperature protection to obey the UL regulations.
9
100 INDUSTRIAL AC drive
®
Overvoltage trip limit
Undervoltage trip limit
Earth fault protection
Mains supervision
Motor phase supervision
Overcurrent protection
Unit overtemperature
protection
Motor overload protection
Motor stall protection
Motor underload protec-
tion
Short-circuit protection of
+24 V and +10 V reference
voltages
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
TECHNICAL DATA, VACON® 100 INDUSTRIAL
Technical data
Mains voltage 240 V: 456 VDC
Mains voltage 500 V: 911 VDC
Mains voltage 690 V: 1258 VDC
Depends on mains voltage (0.8775 x mains voltage):
Mains voltage 240 V: trip limit 211 VDC
Mains voltage 400 V: trip limit 351 VDC
Mains voltage 500 V: trip limit 438 VDC
Mains voltage 525 V: trip limit 461 VDC
Mains voltage 690 V: trip limit 606 VDC
Yes
Yes
Yes
Yes
Yes
Yes. * The motor overload protection activates at 110%
of the full load current.
Yes
Yes
Yes