6.8.2 Network structure MATRIX.Net
Group 2
Group 3
90
A network can consist of one or several (up to 16) groups. Global modules can
also be integrated into the network. The network structure/network topology of
MATRIX.Net must be performed linearly – see "Topologies of network
MATRIX.Net" on page 91.. The maximum extent of the MATRIX.Net network is
shown in Fig. 6-39.
Group 1
Fig. 6-39: Example of maximum extent of the network
At its maximum extent, the network can consist of:
a maximum of 16 unit groups – see "Topologies of network MATRIX.Net" on
page 91.
two digital input modules (MATRIX.DI)
two analog input modules (MATRIX.AI)
two digital output modules (MATRIX.DO)
a central timer (MATRIX.CLOCK)
one extract-air manager (MATRIX.EM)
– up to 16 LON modules (MATRIX.LON).
The arrangement of the unit groups and global modules in the network is arbitrary.
The following factors are critical for the assignment of units, control panels and
global modules to a group:
the setting of the group address switch (refer to the chapter "Commissioning
and Testing" in the relevant operation manual)
– or the assignment of a module input and output to a unit group via the MA-
TRIX.PC service tool (refer to the online help for the service software).
and not the physical assignment.
Group 4
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Flex-Geko Fan Coil Unit
Group 16