DencoHappel ZGF.1E series Operation Manual page 14

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions
2.3.3 Unit and heat exchanger
14
Unit and heat exchanger
Max. operating pressure/temperature
Max. allowed ambient temperature
Min. allowed ambient temperature
Operating voltage
Power consumption/protection class
Max. discharge temperature
Tab. 2-2: Operating limits for unit and heat exchanger
Model
Capacity
size
size
1
2
1
3
4
1
2
2
3
4
1
2
3
3
4
1
2
4
3
4
1
2
5
3
4
1
2
6
3
4
1
2
7
3
4
1
2
8
3
4
Tab. 2-3: Maximum allowed medium flow rate
Maximum medium flow rate [l/h]
2-pipe
cooling or heating circuit
380
760
760
380
380
760
1140
380
760
1140
1140
760
760
1140
1521
760
760
1140
1521
760
1521
2281
3041
1140
1521
2281
3041
1140
1521
2281
3041
1521
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Flex-Geko Fan Coil Unit
Values
1.6 MPa (16 bar)/90 °C
40 °C
2 °C
230 V AC, 50 Hz
Refer to identification plate
75 °C (fire hazard)
4-pipe
cooling circuit
heating circuit
380
760
380
760
760
380
760
1140
380
760
1140
760
1140
1140
760
1140
2281
760
1140
2281
760
1140
2281
760
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents