Flex-Geko Fan Coil Unit
Group structure with MATRIX 3000 and/or MATRIX 4000 system
®
Unit 1
PR-2011-0115-GB • Subject to modifications • R4-12/2015
A group may be formed using the MATRIX 3000 and MATRIX 4000 systems. The
Fig. 6-38 shows an example of a network consisting of a control panel,
MATRIX 3000 system, MATRIX 4000 system and various global modules.
Unit 2
Unit 16
Fig. 6-38: Combined group structure of controller types MATRIX 3000 and
MATRIX 4000
Any assignment and combination of the controllers/units is possible. However,
only MATRIX 3000 or only MATRIX 4000 controllers may be used.We recom-
mend the arrangement of a control panel as the first component of a group.
The group address is assigned:
via the group address switch on the control panel – refer to the "Commission-
ing and Testing" section in the relevant operation manual for DencoHappel
®
MATRIX
on the printed circuit board of the MATRIX 3000/4000 controller – refer to the
unit's operation manual.
Data assignment of MATRIX.LON module is performed via LON
tion. The MATRIX.V, MATRIX.RF and MATRIX.EM modules are assigned to this
group via the group address switch – refer to the "Commissioning" section in this
operation manual or the corresponding manual for DencoHappel MATRIX
Global Modules.
NOTICE!
The combination of units with MATRIX 3000 and units with MATRIX 2000 sys-
tems is permitted in this group setup – see "Group structure of the MATRIX
3000 system in combination with the MATRIX 2000 system" on page 88.. The
combination of units with MATRIX 4000 and units with MATRIX 2000 systems
is not possible
Group
control panels.