DencoHappel ZGF.1E series Operation Manual page 133

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Flex-Geko Fan Coil Unit
Fig. 8-6:
Cleaning Geko-DRIVE
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Maintenance for a ceiling unit should be performed in an analogous way.
Remove the cover plate of the fan chamber (see Fig. 8-4, Pos. 1, 1 screw per
each right and left side) or remove the filter with front-side intake (see Fig. 8-
2, Pos. 1).
Remove the cover plate of the heat exchanger (see Fig. 8-6, Pos. 1, 2 screws
per each right and left side).
Remove the entire Geko-DRIVE assembly (see Fig. 8-6, Pos. 2, 2 screws per
each right and left side), for this purpose damper actuator cable must be pulled
out of the grommet of the electrical control box.
Check the Geko-DRIVE damper assembly for dirt and mould and, if required,
clean and disinfect.
Mount all components in the reverse order
1
NOTICE!
Do not mount components back in place, if subsequent cleaning/disinfecting of
the heat exchanger and main drain pan is required!
Safety and User Instructions
Cover plate of fan
Pos. 1:
section
Cover plate of heat
Pos. 2:
exchanger
Geko-DRIVE
Pos. 3:
3
2
133