7.14.2 Fans with MATRIX 511
7.14.3 Valves
7.14.4 Condensate pump
7.14.5 Standby mode
PR-2011-0115-GB • Subject to modifications • R4-12/2015
The fan control behaviour depends on the selected operating mode on the control
panel.
In position "A" the fan speed 3 is continuously activated.
In positions "1" to "5" the fan is deactivated as soon as the setpoint tempera-
ture is reached. Deactivation is performed by taking into account the minimum
running time (2 min.) and repeated activation following minimum downtime (1
min.).
Depending on the selected controller, the integrated valve controller supports
open/close and modulating valves.
The valves can be controlled in the following modes:
Heating
Cooling
Cooling or heating
Heating and cooling
In order to reach a common starting position, the factory set synchronisation
mechanism moves all connected valves (only modulating valves) to OPEN or
CLOSE position every 12 hours.
The condensate pump drains the condensate that forms on cooling units.
Depending on requirements, the condensate pump is activated by a float switch.
When a limit value is exceeded, the fan is switched off, the cooling valve is closed
and an error message is displayed on the control panel.
Standby mode is only available with room temperature control option. This does
not regulate the temperature to a fixed setpoint, but instead to a pre-set setpoint
range. The DencoHappel MATRIX.PC service software enables to change this
setpoint.
The standby mode is activated if a room temperature sensor is connected but no
room temperature setpoint, i.e. no control panel, is available (e.g. during con-
struction phase and drying of building).
The "standby mode" function is terminated as soon as the fixed room temperature
setpoint is set.
MATRIX
511
2001
3001
MATRIX
511
2001
3001
MATRIX
511
2001
3001
MATRIX
511
2001
3001
Safety and User Instructions
4001
4001+IO
4001
4001+IO
4001
4001+IO
4001
4001+IO
125

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents