DencoHappel ZGF.1E series Operation Manual page 66

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions
Resistance type
[Ω]
600
900
1400
Tab. 6-4: Series resistor types and their setting limits
Changing speed (units of model size 7)
66
NOTICE!
The clearance between adjustable clips should amount to at least 10 mm. The
following setting limits apply to the 3 possible series resistor types (see Tab. 6-
4).
R
max
[Ω]
570
850
1330
Units of model size 7 are fitted with two series resistors.
It must be ensured that the set ohm value is twice as high for all resistor clips of
the side fan (see Fig. 6-3; Pos. 1) than for resistor clips of the middle fan (see
Fig. 6-3; Pos. 2).
DAMAGE TO THE UNIT!
It is not allowed to change speed on any of the series resistors (side or middle)!
Series resistors may burn through!
Fig. 6-3:
Unit with series resistors
Series resistor (side)
Pos. 1:
Series resistor (middle)
Pos. 2:
Changing speed of fan motors: refer to "Changing speed (units of model size
1 ... 6, 8)" on page 69.
R
min
[Ω]
90
180
400
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Flex-Geko Fan Coil Unit
ΔR (between clips)
[Ω]
75
110
170

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents