DencoHappel ZGF.1E series Operation Manual page 102

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions
6.11.7 Configuration
Fig. 6-59: Switch control elements
102
Perform configuration
To change parameters proceed as follows:
set button SEL0 to 10°C
set button SEL2 to position A
press both bottons SEL1 and SEL3 simultaneously for
more than 5 seconds
if the LED H/C has flashed and changed red and green
for 3 seconds, parameters can be changed
for this purpose use SEL0 to adjust the temperature
value for the corresponding parameter and SEL2 to
select the required feature
If this feature is already selected, the LED H/C lights
up green, otherwise red
to save the new feature keep SEL1 pressed until LED
H/C lights up green again and change to the next
parameter, if needed
to save values permanently press SEL1 for more than
5 seconds. Triple flashing of the LED H/C will confirm
the successful saving.
Perform factory setting (see Tab. 6-8, grey column)
set button SEL0 to 10°C
set button SEL2 to position A
press both bottons SEL1 and SEL3 simultaneously for
more than 5 seconds
if the LED H/C flashes and changes red and green,
parameters can be changed
set button SEL0 to 30°C
set button SEL2 to position 2 (red LED flashes fast)
press SEL1 for longer than 5 seconds; factory settings
are restored
PR-2011-0115-GB • Subject to modifications • R4-12/2015