Checking Control Inputs And Outputs - DencoHappel ZGF.1E series Operation Manual

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions

7.10 Checking control inputs and outputs

7.10.1 Functional input
120
The MATRIX 500/3000/4000 control systems are fitted with inputs and/or out-
puts.Consider the factory-performed configuration for checking control inputs and
outputs.Refer to the unit connection diagram (attached to the connection box) for
the relevant controller function.
Field-performed changes of the configuration (via MATRIX.PDA service tool or
MATRIX.PC service software) have to be considered separately (not with
MATRIX 511).
Depending on the control system, the input can be assigned with the following
functions as required:
Window contact (unit OFF with room frost protection); (not with MATRIX
511)
Couple input terminals.
Turn the unit on and adjust the setpoint as required to activate the fan.
Remove the jumper.
The fan must switch off, the valves close
(unit remains in frost-protection monitoring mode).
Economy mode
Turn the unit on and adjust the setpoint as required to activate the fan.
Couple input terminals.
The fan must switch off and valves close.
Requirement: economy mode setpoint adjusted accordingly (unit continues to
operate in frost protection monitoring mode, if this function is available).
NOTICE!
If multiple inputs of different configuration are used within one group, then
"economy mode" input has priority over "window contact" input.
MATRIX
511
2001
3001
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Flex-Geko Fan Coil Unit
4001
4001+IO