Flex-Geko Fan Coil Unit
7.2.2 Shut-off valve settings (variants)
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Check if shut off valves are open:
•
Unscrew the protective cap (Fig. 7-2, Pos. 2).
•
Close the valve by tightening the internal flow-control screw (Fig. 7-2, Pos. 3)
using a 4 mm hex key until the stop position on the right side.
•
Tighten the pre-setting screw (Fig. 7-2, Pos. 4) until the stop position on the
right side.
•
Perform adjustment by rotating as specified in the diagrams (see Fig. 7-3 with
Tab. 7-2 and Fig. 7-4 with Tab. 7-3). Turn the pre-setting screw in a counter-
clockwise direction (max. 8 turns).
•
Use the hex key to open the flow-control screw (Fig. 7-2, Pos. 3) until the stop
position.
•
Screw the protective cap back on.
Fig. 7-2:
Adjusting shut-off valves
Stop valve
Pos. 1:
Protective cap
Pos. 2:
Flow-control screw
Pos. 3:
Pre-setting screw
Pos. 4:
NOTICE!
Regulation of the medium flow is performed by operating the shut off valve.