DencoHappel ZGF.1E series Operation Manual page 86

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions
6.7.14 Connecting function inputs and outputs
Fig. 6-34: Connecting function input
L
4A
Fig. 6-35: Wiring function inputs and outputs
86
Function input
as
volt-free contact
N
Heating
D33[233]
D32[232]
Jumper on-site by
D00[100]
N
Cooling
D31[231]
D30[230]
Jumper on-site by
D00[100]
D2[62]
Autonomous ope
D3[63]
D4[64]
Unit OFF
D5[65]
D6[66]
Economy mode
D7[67]
D8[68]
Normal opera-
D9[69]
511
2001
Function input can be assigned with different functions
depending on the supplied control equipment.
To activate the function the contact must be:
closed for economy mode operation
open for unit OFF with frost protection
be.
This function can be changed using the service tool
MATRIX.PDA or service software MATRIX.PC.
Connect in accordance with the wiring diagram.
The loop resistance may not exceed 500 Ω.
511
2001
Function inputs
Functional inputs can be assigned with different functions:
normal operation
economy mode
autonomous operating mode (functions of these oper-
ating modes can be programmed using the service soft-
ware MATRIX.PC)
switching the unit off (without frost-free condition in
room)
Function outputs
The control contains 2 function outputs:
heat request (max. 230 V/4 A ohmic/
2 A inductive)
cooling request (max. 230 V/4 A ohmic/
2 A inductive)
If no jumpers are set at 100-230 and 100-232, outputs 230-
231 and 232-233 can be used as volt free outputs (max. 2
A).
Connect in accordance with the wiring diagram.
The loop resistance may not exceed 500 Ω.
PR-2011-0115-GB • Subject to modifications • R4-12/2015