DencoHappel ZGF.1E series Operation Manual page 70

Flex-geko economy series; flex-geko comfort series decentral systems comfort - fan coil units
Table of Contents

Advertisement

Safety and User Instructions
6.4.3 Regulation of EC motor in units with an electric heater
70
Model size
Number of motors
Tab. 6-5: Number of motors
Only connecting terminals for motor(s) are shown. Refer to the unit-specific wiring
diagram for wiring other connecting terminals. If a unit is fitted with one motor, an
alarm signal is conducted to the terminals 11.1. If a unit is fitted with two motors,
alarm signals are conducted to terminals 11.1 and 11.2. Individual alarm signals
are ground-referenced. In a trouble-free state the output transistor is closed, the
signal is wired to terminals 11.1 or 11.2 and connected to ground (identical to
potential on terminal 11.5).
If a PWM (pulse-width modulation) signal is used for regulation, the latter must
feature a basic frequency between 1 KHz and 10 KHz. At < 10% pulsing the
speed amounts to 0; at 14% the motor is running at n
running at n
max
When actuated with a 0-10V signal, consider that the speed is = 0 for an input volt-
age of less than 1V; if voltage amounts to 1.4V the motor is running at n
10V the motor is running at n
NOTICE!
A maximum of 10 mA current and 30 V voltage can be applied to malfunction-
report outputs. In a trouble-free state the output transistor is closed (E, C path).
According to the relevant regulations, an all-pole isolating device must be pro-
vided by others on site. If an earth leakage circuit breaker is used, all-current
sensitive types (type B) must be used.
In units with an electric heater the following minimum control signal size must be
maintained:
Model size
Auxiliary electric heater
Speed 1
Auxiliary electric heater
Speed 2
Full electric heater Speed 1
Full electric heater Speed 2
Tab. 6-6: Minimum control signal with electric heater
DAMAGE TO THE UNIT!
If minimum control signal size is not maintained, units can sustain damage.
1
2
3
1
1
1
.
max
1
2
3
25%
22%
25%
49%
44%
63%
35%
77%
38%
100%
100%
100%
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Flex-Geko Fan Coil Unit
4
5
6
1
1
2
; at 100% the motor is
min
4
5
6
20%
19%
23%
54%
54%
51%
31%
32%
35%
100%
100%
79%
7
8
2
2
; with
min
7
8
23%
24%
52%
64%
34%
38%
86%
100%