Flex-Geko Fan Coil Unit
PR-2011-0115-GB • Subject to modifications • R4-12/2015
Minimum heating limitation (rigid):
The set minimum temperature value is maintained (value does not fall below
limit).
Advantage: Air draughts are largely avoided.
Disadvantage: The room can become slightly overheated, particularly if the
set values are too high, as the controller is not able to prevent overheating
using cooler air.
Minimum heating limitation (variable):
Value can fall below the set minimum temperature value if the current room tem-
perature value exceeds the setpoint by a value that is calculated as room tem-
perature difference multiplied by effective factor.
Advantage: Overheating of the room can be prevented or minimized by means
of the minimum limitation.
Disadvantage: The supply-air temperature can fall below the minimum limita-
tion temperature value.
Factory setting and enter limits for effect factor:
Default value
Minimum entered value
Maximum entered value
Maximum heating temperature
If this function is activated and a temperature sensor is present in supply air, a
temperature value can be entered here. This value should not exceed the supply-
air temperature.
Factory setting and entered limit values:
Default value
Minimum entered value
Maximum entered value
Minimum cooling temperature
If this function is activated and a temperature sensor is present in supply air, a
temperature value can be entered here. This value should not fall below the sup-
ply-air temperature.
Factory setting and entered limit values:
Default value
Minimum entered value
Maximum entered value
1.0
0.4
4.0
60.0 °C
25.0 °C
60.0 °C
10.0 °C
10.0 °C
20.0 °C