Brake Resistor Connection Data For Frames R1; Control Connection Data - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

Brake resistor connection data for frames R1...R3
Short-circuit protection
(IEC/EN 61800-5-1, IEC 61439-
1)

Control connection data

External power supply
+24 V DC output
(Term. 10)
The brake resistor output is conditionally short-circuit proof by
IEC/EN 61800-5-1. Rated conditional short-circuit current as
defined in IEC 61439-1.
Maximum power:
Frames R1...R5: 25 W, 1.04 A at 24 V AC/DC ±10% with an
option module
Frames R6...R9: 36 W, 1.50 A at 24 V AC/DC ±10% as stand-
ard
Supplied from an external power supply through option module
CMOD-01 or CMOD-02 with frames R1...R5. With frames
R6...R9 no options are needed.
Terminal size:
Frames R1...R5: 0.2...2.5 mm 2 (24...14 AWG)
Frames R6...R9: 0.14...2.5 mm 2 (26...14 AWG)
Total load capacity of this outputs is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on the
board.
Terminal size:
Frames R1...R5: 0.2...2.5 mm 2 (24...14 AWG)
Frames R6...R9: 0.14...2.5 mm 2 (26...14 AWG)
Technical data 291