Energy Monitoring And Motor Protection - MultiTrode MultiSmart Installation & Operation Manual

Pump station manager & rtu
Hide thumbs Also See for MultiSmart:
Table of Contents

Advertisement

10.4.5
Profiles
The pump control module supports six (6) profiles. Each profile consists of pump activation/deactivation
setpoints, as well as four station optimization functions (Max Off Time, Max Run Time, Station Max Pumps to
Run & Well Clean Out). Profiles can be switched via any of the following methods: (See Section 15 for more
information).
User interface
SCADA
A timer (e.g. time of day)
Digital input (e.g. a switch on the panel) or any digital tag (e.g. an alarm condition)
Logic engine script or ISaGRAF program
10.4.6
Station Optimization Functions
Many desirable functions are pre-defined, with the user simply enabling/disabling or choosing parameters for
the functions. These functions include:
Pump Reversal (to avoid blockages)
Odor Reduction (via maximum off time)
Maximum Run Time
Station Maximum Pumps to Run (for electrical or hydraulic overload protection)
Minimize Fat Buildup (via random duty start)
Well Clean Out
Minimize Excessive Starts
High Inflow
Well Washer
Well Mixer
Blocked Pump Detection
Pump n Max Starts per Hour
See Section 16 for more information.
10.4.7
Watchdog
The pump control module includes a watchdog function which counts up while the pump control module is
functioning. This value is available as a tag in DNP3 and Modbus so that a SCADA system can monitor the
health of this module.

10.5 Energy Monitoring and Motor Protection

An optional Energy Monitoring Motor Protection module in conjunction with a Motor Protection card can be
supplied with the MultiSmart pump station manager. The module monitors currents and provides protection
from:
Over and Under Current
Over Current I
Current Phase Imbalance (or Phase Failure)
Current Phase Rotation
Ground (Earth) fault
This module also periodically tests the insulation resistance of the motor windings. Two user defined
thresholds can be entered one for a warning message and a second for a fault message, neither or both can
be configured to fault a pump if the IRT value falls below the thresholds.
Page 78 of 260
MultiSmart Installation & Operation Manual
2
T
MultiSmart_IO_Manual_R20

Advertisement