Commissioning
4.4 Extended Safety
● Set the following in this screen:
● Close the screen.
4.4.1.11

Activate settings

● Click "Copy parameters" and then click "Activate settings":
● If the password = 0 (factory setting), follow the prompts in order to set a password.
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the Control Unit power supply for approximately 10 seconds (Power ON
92
Setpoint speed limit as a % of the monitoring threshold.
This parameter defines the upper speed limit when SLS is active.
Monitoring threshold
Enter the load-side speed to be monitored. The inverter calculates the maximum
motor speed on the basis of this parameter and the gear ratio.
Response when monitoring is activated. Further information on the stop responses
can be found in the section STOP reactions (Page 137).
– A functional description of monitoring can be found in the section Selecting SLS when
the motor is switched on (Page 24).
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 40).
Reset). Only then will your changes become effective.
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA