2.7.6
Switching the motor on and off when SLS is active
Proceed as follows to switch the motor off and on again when SLS is active:
● Switch the motor off when SLS is active.
● When the motor has come to a standstill, activate STO.
● Deselect STO before switching the motor on again.
● Switch on the motor within 5 seconds (ON command).
If you do not switch on the motor within 5 seconds, the inverter switches to the STO status
again and does not respond to the ON command. To switch the motor on again, proceed as
follows:
● Select STO.
● Deselect STO.
● Switch on the motor within 5 seconds (ON command).
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
Figure 2-16
Switching the motor on and off when SLS is active
Description
2.7 Interrupting safety functions
39