Completion of certificate

Document your machine's data for each drive based on the following specifications.
Parameters of the safety functions
The function test does not detect all faults in the parameter assignment of safety functions,
e.g. forced dormant error detection time or filtering time of fail-safe inputs. Therefore, check
all parameters once more.
Labeling the drive
...
...
Checksums of the safety functions
The inverter calculates checksums across all parameters and safety functions. The
parameters of Basic Safety and Extended Safety have their own checksums.
When you change the safety function settings, the inverter calculates new checksums. This
means that subsequent changes in your machine can be tracked.
In addition to the individual checksums of the parameters, the inverter calculates and saves
the following values:
1. The "total" checksum across all checksums.
2. Time of the last parameter changed.
Labeling the drive
Processor 1
...
p9798
p9799
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
Basic Safety
Processor 2
Processor 1
p9898
p9398[0]
p9899
p9399[0]
4.8 Acceptance test - Completion of commissioning
All parameter values checked
Checksums
Extended Safety
Processor 2
[0] = Parameter
[1] = Actual
values
p9728[0]
p9728[1]
p9729[0]
p9729[1]
Commissioning
Total
Time stamp
r9781[0]
r9782[0]
125